Double Stage Vacuum Transformer Oil Regeneration Plant

Product Details
Customization: Available
Certification: CE
Application: Transformer Oil
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2020

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

100% Finished Products Inspection
The supplier inspects 100% of finished products.
Standardized quality control
The supplier has a complete and standardized quality control process, check the Audit Report for more information
R&D Capabilities
The supplier has 3 R&D engineers, you can check the Audit Report for more information
Production Process Visualization
You can check the supplier's production workflow chart or main facilities in the Audit Report
to see all verified strength labels (27)
  • Double Stage Vacuum Transformer Oil Regeneration Plant
  • Double Stage Vacuum Transformer Oil Regeneration Plant
  • Double Stage Vacuum Transformer Oil Regeneration Plant
Find Similar Products
  • Overview
  • Product Description
  • Product Parameters
  • Reference Images
Overview

Basic Info.

Model NO.
ZYD-I
Folw Rate
30 L/min
Transport Package
Wooden Case
Specification
depend on model
Trademark
Chongqing TOP Oil Purifier
Origin
China
HS Code
842129
Production Capacity
20 Sets/Month

Product Description


 
Product Description

Application:
The Oil regeneration system (Series ZYD-I) has been specially designed for on site use to completely regenerate insulating oils in energized or de-energized transformers. The ZYD-I system provides regular oil purification such as degassing, drying and particulate removal but also can remove acidity, sludge, other soluble oil decay products and discoloration. This is accomplished by the use of high vacuum degasification technology and particulate filters combined with our special brand of earth. After treating, the oil can be reused as new. 

Features:

1.The plant is delivered ready for operation.
2. Degassing, dehydration and filtering  process if various kind of insulation oils in electrical transformers and circuit breakers through put in one or several passes

3. There are two vacuum pumps for plant ZYD-I (one is the vacuum pump, other one is the booster roots pump), which can improve the vacuum value highly. Making sure the water-content of the treated oil is less than 3 PPM.
4. All oil treatment plants, type ZYD-I are equipped with an automatic Anti-Foam Control System. 
5. The plant is equipped with built-in control and safety devices, which provides for a maximum operating security.
6.  Minimised power consumption through optimised degassing (excellent efficiency factor).
7. Standardized filter housing for 1 micron , 5 micron, 20 micron and 80 micron filter cartridges.
8. Automatic supervision of the degree of contamination of the fine filter cartridges
9. ZYD-I can evacuate the vacuum for the electric equipments separately, such as the transformer. Also it can be used to dry the electric equipment and input the oil into the electric equipment under the vacuum state.
10. The machine adopts the double-infrared liquid automatic controller, pressure automatic-protector which
can make sure the machine works online for 150 hours continuously without person. So it is a reliable and
high automatically machine.
11. Adopt interlocked protective system, which connect oil pump, heater and liquid level sensor, avoiding blank heating, blank pumping, oil leak and electricity leak. If there is any fault, machine will be power off automatically.
12. Functions of live line work on-site, vacuum drying and vacuum oiling.
13. Operational can be P.L.C (Programmable Logic Controller). (optional)
14. On-line water content measuring device (optional)
15. Regeneration system BZ with special brand of earth can remove acidity, sludge, other soluble oil decay products and discoloration
 

Product Parameters
Parameter Unit ZYD-I-30 ZYD-I-50 ZYD-I-100 ZYD-I-150 ZYD-I-200 ZYD-I-250 ZYD-I-300  
Flow rate L/h 1800 3000 6000 9000 12000 15000 18000  
Work vacuum MPa -0.08~-0.099  
Work pressure MPa ≤0.3  
Temperature ºC 20 ~ 80  
Power   3 ph 380V 60Hz (Or as needed)  
Working noise dB(A) 75 75 75 75 80 80 80  
Heating power kW 30 30 45 60 75 90 120  
Total power kW 35.5 37.5 52.5 71.4 86.5 102.5 135  
Oil Inlet/Outlet  mm φ25 φ32 φ42 φ50 φ50 φ60 φ60  
Weight Kg 600 800 1050 1400 1800 2000 2200  
Size Length mm 1050 1100 1200 1450 1600 1800 1900
Width mm 750 800 950 950 1100 1200 1200
Height mm 1350 1400 1500 1650 1800 1900 1900
Item Unit After treatment
Breakdown Voltage kV ≥75
Moisture content PPM ≤3
Gas content % 0.1
Impurity size micron ≤1 (no free carbon)
IFT dynes/cm ≥40
Acid value mg KOH/g ≤ 0.03
Dielectric loss factors tgδ(90ºC) ≤0.001
Reference Images

 

Double Stage Vacuum Transformer Oil Regeneration PlantDouble Stage Vacuum Transformer Oil Regeneration PlantDouble Stage Vacuum Transformer Oil Regeneration Plant