Mobile Two-Stage Insulating Oil Filtration Plant (ZYD-M-50)
1. Dehydration, degasing, remove out particles, residuals and other impurities in oil
2. Improve insulator oil's dielectrical stregth; (more than 75KV)
3. Can also serve as transformer oil filler and dryer for transformer. Mobile type vacuum Transformer oil recycling machine mounted on trailer remove the water, gas and impurities in insulating oil
Series ZYD-M Mobile type Double-stage vacuum Transformer oil purifier can remove the water, gas and impurities in insulation oil high-efficiently, increasing the pressure force and quality of oil, make the oil limiting voltage-withstand value much higher and make sure the electric device running safely. The machine is mainly used for electric power department and industries to deal with various oils such as transformer oil, mutual oil, switch oil, dielectric oil, insulating oil and so on. It also can be used for filtration of more than 110KV substation live line work onsite. Meanwhile, as the bridge-type vacuum linking system, Series ZYD-M oil purifier can be used as independent vacuum source with functions of vacuum drying and vacuum oiling.
Comparing with the single stage type, this machine adopts the double stages vacuum system, which can improve the machine working vacuum value highly, so it can remove the water, gas and impurities in insulating oil high-efficiently, increasing and maintain the oil's dielectric strength more higher.
According to fieldwork requirement, this machine equips car wheels, which can be easily moved to any work point by traction. It is especially suitable for purifying oil which locates in fields.
(oil filtration, oil purification, oil treatment, oil purifier, oil filter, oil recycling, oil processing, oil filtering, oil purifying, oil regeneration, oil filteration, oil purify, energy saving, oil processor, oil filter, oil process, oil regenerating, oil restoration, waste oil disposal, oil reclaimed, oil reclaiming, waste oil management, oil regenerate, oil reconditioned, oil reconstituted, oil restituting, oil recovering, oil recondition, oil filters, oil refinery, oil refiner, oil cleaning, oil recycle, oil reclaiming, oil separator, oil recovery, oil recycle, oil reclamation, oil refinery, oil separator, oil separation, oil purifiers, oil recondition)
Our oil filtration machine:
Series ZY Single-Stage Vacuum Transformer Oil Purifier
Series ZYD Double High Vacuum Transformer Oil Purifier
Series ZYB Multiply-Function insulating oil treatment machine
Series TY Turbine Oil Purification Apparatus
Series TYA Lubricating oil/ hydraulic oil purification unit
Series TYB Portable light Fuel oil purification machine
Series TYD Vacuum dehydrator
Series TYF Phosphate ester fire-resistance oil purifier
Series PL Plate pressure oil purifier
Series TYD Vacuum dehydrator
Series EFD Explosion protection filtration machine
Series BAM Press filtration system
Series ZKCC Vacuum pumping device
Series COP Cooking oil purification machine
Series CYS Centrifugal oil purification machine
Series JL Portable oil filtering and oiling machine
Series EOR series waste engine oil recycling system
Test equipment
1. Transformer oil Breakdown voltage Tester ( BDV test kit) series IIJ-II
2. Acidity tester model ACD-3000I
3. Karl Fischer Water content Tester Model TP-6A / model TP-2100
4. Fully automatic Interfacial Tension Analyzer model IT-800
5. Gas-Chromatography transformer oil gas analyzer model DGA2013-1
6. Kinematic Viscosity tester model VST-8 /model VST-2000
7. Flash point tester (open cup) model TPO-3000
8. Flash point tester (close cup) model TPC-3000
9. TAN-DELTA TESTER, 10kV Capacitance and Dissipation Factor Test Set model CDEF
10. CT/PT tester model TPVA-404
11. Transformer turn ratio tester model HYG-II
12. Relaying Protection Tester model TPJB-III
Technical data |
ZYD-M -30 |
ZYD-M -50 |
ZYD-M -75 |
ZYD-M -100 |
ZYD-M -150 |
ZYD-M -200 |
ZYD-M -300 |
ZYD-M -500 |
ZYD-M -1000 |
Rated Flow rate (L/h) |
1800 |
3000 |
4500 |
6000 |
9000 |
12000 |
18000 |
30000 |
60000 |
Heating Power (kw) |
30 |
42 |
54 |
60 |
84 |
108 |
156 |
225 |
450 |
Total Power (kw) |
33 |
46 |
60 |
67 |
94 |
119 |
173 |
257 |
511 |
Inlet(outlet) Dia.(mm) |
25 |
32 |
40 |
40 |
50 |
50 |
65 |
80 |
100 |
Dimensions(cm) |
L |
1380 |
1500 |
1750 |
1900 |
2100 |
2300 |
2600 |
3200 |
3600 |
W |
1100 |
1200 |
1250 |
1280 |
1300 |
1300 |
1380 |
1500 |
1600 |
H |
1600 |
1650 |
1650 |
1700 |
1800 |
1850 |
1950 |
2100 |
2300 |
Net Weight (kg) |
600 |
800 |
900 |
1050 |
1500 |
1800 |
2200 |
3960 |
4980 |
Notice: Due to different type and components of product, the technical data may vary slightly.
Guarantee Performance Index
Insulation Oil Before Treatment |
After One Time Treatment |
After the Treatment of few Times |
Water Content in the Oil ≤ 50PPm |
≤ 15PPm |
≤ 3~5PPm |
Gas Content in the Oil ≤ 12% |
≤ 0.5% |
≤ 0.1% |
Flash Point ≤ 135 C |
≥135 C |
≥135 C |
Breakdown Voltage ≥35kv |
≥55kv |
≥60 ~75kv |