Transformer Oil Vacuum Dehydration Regeneration Plant(ZYB-50)
Specifications:
Transformer oil vacuum dehydration machine
1. Remove various impurities, improve oil breakdown voltage
2. Multi-function
3. Get ISO; CE
Description:
Series ZYB is applied to purify and regenerate the used insulating oils includes transformer oil, switch oil, circuit breaker oil, capacitor oil, mutual inductor oil in power generation plants, transformer stations, electric transmission and supplying company, factories, mines, railway transportation, etc. It can be used as special equipment for electric power transformer maintenance. Not only can it remove water, gas, and other impurities from the oil, but also it can remove oxide materials and remove free carbon in the deteriorated oil to lower the PH value, improve its breakdown voltage and quality, recovery the oil color. After treating, the insualting oil can reach international standard and recover its original function.
Features:
Hi-efficient degassing, dehydration system, remove water, gas and impurities effectively
Precise multi-stage filtration system, high-quality filter element, big pollutant containing capacity
Add special absorbing agent to remove polarity materials, such as free carbon, water- Soluble acid and so on, so as to improve flash point, acid value and dielectric strength, recover some oil index to normal, like anti-oxides, acid-alkali water solubility, achieve oil regeneration, avoiding waste and pollution
Combined electric heating system with swirling heating system, achieving quick and even heating on constant temperature.
Adopts interlocked protective system, which connects oil pump, heater, and liquid level sensor, avoiding blank heating, blank pumping, oil leak, electricity leak. If there is any fault, machine will be power off automatically. So it is safe and reliable machine.
Applied to used insulating oil even seriously deteriorated oil purification and regeneration, suitable to transformer oil purification onsite and online
Three ways of using: Vacuum dewatering, degassing, impurities removal system can work independently; Regeneration system can work independently; Both can work at the same time.
Also can be used for vacuum pumping and oil filling for transformers.
Advantages:
It can not only removing the water, gas and impurities which mixed in the oil, but also can improve many values to the national standard such as the acid value, PH value. Meanwhile, it improves the voltage-withstand value through filtering the polarity materials like free carbon, deep oxides and so on so as to achieve oil regeneration, extend oil performance lifetime.
Why do we choose oil purifier?
After a period of operation, owing to its exposal to oxygen and mixed with water, copper and iron and other foreign materials and high working temperature acceleration, transformer oil will oxidize and lose its original property and cannot be used effectively again. So TOP oil purifiers can efficiently remove water, dirt, gases and other foreign impurities from oil, such as de-electrical oil, turbine oil, lubricating oil, engine oil, hydraulic oil, compression oil, mechanical oil, quenching oil, heat conducting oil, gear oil etc; So as to maintain its lubricating and insulating property, then to reduce components wear, and cut down oil expenses.
What Oil can we process?
We can process turbine oil, transformer oil, insulation oil, switch oil, capacitor oil, gear oil, vacuum pump oil, bunker oil, engine oil, hydraulic oil, black oil, diesel, freezer oil, compressor oil, vacuum pump oil, heat treatment oil, fire-resistant oil, machinery oil and other lubricant oils.
Parameters |
Unit |
ZYB-20 |
ZYB -30 |
ZYB -50 |
ZYB -100 |
ZYB -150 |
ZYB -200 |
Capacity |
L/h |
1200 |
1800 |
3000 |
6000 |
9000 |
12000 |
Vacuum pressure range |
Mpa |
- 0.08 ~- 0.095 |
Pressure working |
Mpa |
≤ 0.3 |
Temperature range |
°C |
10 ~ 80 |
Working noise |
dB(A) |
≤ 68 |
≤ 70 |
≤ 72 |
≤ 75 |
≤ 80 |
≤ 80 |
Heating power |
kW |
18 |
24 |
30 |
45 |
60 |
72 |
Total power |
kW |
22 |
28 |
35 |
50 |
68 |
80 |
Oil inlet (outlet) caliber |
mm |
Ø25 |
Ø25 |
Ø32 |
Ø42 |
Ø50 |
Ø50 |
Dimension |
L |
mm |
1500 |
1600 |
1600 |
1600 |
1600 |
1700 |
W |
mm |
900 |
900 |
900 |
950 |
950 |
1000 |
H |
mm |
1550 |
1650 |
1700 |
1700 |
1800 |
1900 |
Weight |
kg |
400 |
450 |
600 |
800 |
850 |
900 |
Guarantee value
Moisture |
PPM |
≤ 5 |
Gas content |
% |
≤ 0.1 |
Impurity size |
μ |
≤ 1 (no free carbon) |
Breakdown voltage |
kV |
≥ 70 |
IFT |
dynes/cm |
≥ 40 |
Acid value |
mgKOH/g |
≤ 0.03 |
Dielectric loss factors |
tg δ (90 °C ) |
≤ 0.001 |