CT/PT volt-ampere characteristic curve test,
CT/PT Polarity test,
CT/PT Transformation ratio test
automatically calculate error curve of any CT point
Specifications
Automatic transformer test set (TPVA-402)
-test volt-ampere characteristic curve, polarity, ratio etc.
-For CT/PT test
General introduction
TPVA-402 is a fully automatic transformer comprehensive tester. The tester can finish: CT/PT volt-ampere characteristic curve test, CT/PT Polarity test, CT/PT Transformation ratio test, automatically calculating error curve of any CT point.
Characteristics
1 This TPVA-402 transformer tester is easy to operate. Complete computerize device and high performance CPU,no need manual work,it finishes test automatically,which prevent person from high voltage circuit.
2 Large output. Maximum output voltage of volt-ampere characteristic test reaches to 1000V,Maximum output current of transformation ratio test is 600A,output capacity of internal voltage regulating machine is 5KVA.
3 Optional accessory includes external join to voltage raising machine ,current raising machine and voltage regulating machine.Maximum voltage of external voltage raising machine is 2000V,3A;Maximum current of external current raising machine is 1000A;Maximum output of external voltage regulating machine is 1500V,20A.You can have a CT test of reach up to 500KV,1A when using external voltage raising machine.
4 320*240 Large screen,it can display volt-ampere characteristic curve directly when the test is finished.It can print curve and result anytime with micro-printers of the tester.
5 Adapt rotating mouth,easy operation and durable use.
6 Flash Ram inside,prevent data losing from power off.
7 RS232 communication interface,make sure connection of the instrument and PC,triers can control the test and unload the test data through PC.
8 AC220V and AC380V power supply
Parameters
|
Input voltage |
Output scope |
Measuring scope |
Measuring degree |
Device main engine |
220V |
0~600V,0~20A |
0~600V,0~20A |
0.5% |
380V |
0~1000V,0~20A |
0~1000V,0~20A |
0.5% |
220V |
0~600A |
0~600A |
Transformation ratio measuring precision 1% |
External voltage raising machine |
220V |
0~1650V,0~3A |
0~1650V,0~3A |
0.5% |
380V |
0~2000V,0~3A |
0~2000V,0~3A |
0.5% |
External current raising machine |
220V |
0~1000A |
0~1000A |
Transformation ratio measuring precision 1% |
External voltage adjustment machine |
|
|
0~1000V,0~30A |
0.5% |
Device working power |
AC 220V/380V 50HZ |
External dimensions |
420×330×320mm |
Weight |
24kg |
Our Major Testing Equipment
1.Transformer oil breakdown voltage tester ( BDV test kit) series IIJ-II
2. Acidity tester model ACD-3000I
3. Karl Fischer water content tester model TP-6A / model TP-2100
4. Moisture content tester(TPEE)
5. Fully automatic interfacial tension analyzer model IT-800
6. Gas-chromatography transformer oil gas analyzer model DGA2013-1
7. Consolidation point determinator model PT-2000
8. Kinematic viscosity tester model VST-8 /model VST-2000
9. Flash point tester (open cup) model TPO-3000
10. Flash point tester (close cup) model TPC-3000
11. Transformer tester (CT/PT tester) model TPVA-404
12. Transformer turn ratio tester model HYG-II
13. Total base number analyzer(TBN tester) TBN-2030
Our instrument has been sold all over the world and gets very good feekback, welcome to check, we will offer the best price and good quality.