Transformer Oil Dielectric Loss and Resistivity Testing Instrument (TP-6100A)

Electrode Gap: 2mm
Liquid Capacity: 40ml
Measured Temperature Range: 0~125 Celsius
Electric Capacity: 5PF~200PF
Transport Package: Wooden Case
Specification: CE/ISO
Customization:
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2020

Suppliers with verified business licenses

Rating: 5.0/5
Chongqing, China
100% Finished Products Inspection
The supplier inspects 100% of finished products.
Standardized quality control
The supplier has a complete and standardized quality control process, check the Audit Report for more information
R&D Capabilities
The supplier has 3 R&D engineers, you can check the Audit Report for more information
Production Process Visualization
You can check the supplier's production workflow chart or main facilities in the Audit Report
to see all verified strength labels (27)

Basic Info.

Model NO.
TP-6100A
Trademark
TOP
Origin
China(Mainland)
HS Code
9027809900
Production Capacity
200/Month

Product Description

Transformer  Oil Dielectric Loss and Resistivity test instrument(TP-6100A)


Product Application
TP-6100A Insulating oil dielectric loss and resistivity tester, TP-6100A  is based on IEC and GB/T5654-2007 design and manufacturing of Liquid insulating material of relative permittivity, dielectric loss factor
and DC resistivity measurements. Used for measuring the insulation oil and  other  dielectric loss  factor  of liquid insulating medium and DC resistivity. The instrument is characterized by integrated structure, and
integrates the dielectric loss of grease cup, temperature controller, temperature sensor, dielectric loss test  bridge, AC test power, standard capacitor, high resistance meter, DC high voltage source and other major
components. The instrument adopts full digital technology and all of the intelligent  automatic  measurement,  is equipped with large screen (240*128) LCD display , the test results can be automatically stored and printed  output, so that the operator without professional training will be able to use it proficiently.
Transformer Oil Dielectric Loss and Resistivity Testing Instrument (TP-6100A)


Product Features
1.Grease cup used in line with the national standard GB/T5654-2007 of the three-electrode  structure,  inter-electrode spacing 2mm, can eliminate the  stray capacitance and leakage effects on  dielectric loss  test results

2.The instrument adopts the medium frequency induction heating, PID temperature control algorithm.  This  heating method has the advantages of the oil cup and the heating body non-contact,  even heating,  fast  speed, convenient control, strict control of the temperature in the temperature error within the preset range.

3.Internal standard capacitor of SF6 gas-filled three-electrode  capacitance of the  capacitor dielectric loss  and electrical capacity independent of ambient temperature, humidity and other effects, the instrument
accuracy is ensured even after prolonged use.

4.AC test power supply using AC-DC-AC conversion, effectively  avoid the fluctuations in mains  voltage and  frequency on dielectric loss measurement accuracy effect. Even a generator, the instrument can work properly.

5.Perfect protection function; When there is over voltage,over current or high-voltage short circuit,  instruments  can quickly cut off pressure, and issues a warning message. When the temperature of the sensor failure or
not connected, the instrument will also issue a warning message.

6.There is a temperature limiting relay in the medium frequency induction heating furnace. When temperature  above 120 degrees, the instrument frees the relay and stops heating.

7.More convenient the experimental parameter is set. Temperature setting range 0~125ºC, AC  voltage setting  range 500~2200V, DC voltage setting range 0~500V.

8.Using a large-screen LCD display with backlight,  clear display. Friendly interface, simply follow  the Chinese  menu prompt, enter the command, the instrument can be automatically tested. And automatically store and  print test results.

9.Built-in real-time clock, the test date, time may be retained with the test results, display and print.

10.Air electrode cup calibration function. Measurement of air electrode cup capacitance and dielectric  loss factor, in order to determine air electrode cup cleaning and assembly condition. The calibration data  is automatically saved, in order to facilitate the calculation of relative permittivity and DC resistivity.



Safety Measures

1. using electromagnetic induction heating technique, even heating, fast temperature rise speed,
short time.
2. the output voltage 500V ~ 2000V is continuous and adjustable, suitable for different sample the
voltage level required.
3. the temperature control is accurate, is not affected by environment temperature influence.
4. high measurement accuracy, stable, reproducible data.
5. a boot detection circuit, no grounding or earthing is not good to give a hint.
6. a short-circuit protection circuit, short circuit and high voltage output circuit.

Technical Parameter
Electrode gap :       2mm
Maximum working voltage:2KV,50HZ
The empty cup capacitance:60±5pF
The empty cup dielectric loss  : ≤5×10-5
Liquid capacity      :40ml
Power supply voltage:AC220V±10%

Power frequency:50Hz/60Hz ±1%

Measuring range:

Electric capacity    5pF~200pF

Relative capacitivity1.000~30.000

Dielectric loss factor0.00001~100

DC Resistivity 2.5MΩm~20TΩm

Measuring accuracy:

Electric capacity± (1% of reading +0.5pF)

Relative capacitivity±1% of reading

DC Resistivity±10% of reading

Resolution:

Electric capacity 0.01pF

Relative capacitivity 0.001

Dielectric dissipation factor 0.00001

Measured temperature range:0~125ºC

Temperature measurement error:±0.5ºC

Test Voltage AC(RMS):500~2200V Continuously adjustable, frequency 50Hz

Test Voltage DC:0~500V  Continuously adjustable

Power dissipation:100W

External dimensions:500×360×420

Total weight:22Kg


Procuct Diagram


1. the high voltage pole ( outer electrode )
2. the measuring electrode ( electrode )
3. insulating magnetic column ( high frequency porcelain )
4. a compression nut
5. shielding electrode
6. an insulating magnetic column ( high frequency porcelain )
7. Mounting body
8. a mounting body of measuring electrode leading-out terminal

 
Our oil filtration machine: 
Series ZY Single-Stage Vacuum Transformer Oil Purifier
Series ZYD Double High Vacuum Transformer Oil Purifier
Series ZYB Multiply-Function insulating oil treatment machine
Series TY Turbine Oil Purification Apparatus
Series TYA Lubricating oil/ hydraulic oil purification unit
Series TYB Portable light Fuel oil purification machine
Series TYD Vacuum dehydrator
Series TYF Phosphate ester fire-resistance oil purifier
Series PL Plate pressure oil purifier
Series TYD Vacuum dehydrator
Series EFD Explosion protection filtration machine
Series BAM Press filtration system
Series ZKCC Vacuum pumping device
Series COP Cooking oil purification machine
Series CYS Centrifugal oil purification machine
Series JL Portable oil filtering and oiling machine 

Our oil tester/ analyzer:
Series IIJ-II Insulating oil breakdown strength tester(oil BDV tester)
Series HTJS-H Insulating oil dielectric tester (dielectric loss tester for insulating oil)
Series HTJS-V Tan-Delta Tester (anti-jamming dielectric loss tester for HV electrical equipment)
Series TP-3A Water content tester/ moisture sensor
Series TPV-8 Viscosity analyzer
Series TPC-2100 Flash point analyzer (close cup)
Series TPO-2100 Flash point analyzer (open cup)
Series CL-3 Interfacial tension analyzer
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now