Vacuum Degasifier Mobile Insulating Oil Treatment Equipment(ZYM-50)
Specifications
Insulating oil treatment equipment
1. Clean transformer oil, mutual oil, switch oil, dielectric oil, insulating oil
2. Low cost
Mobile type vacuum Transformer oil recycling machine mounted on trailer remove the water, gas and impurities in insulating oil
Series ZYD-M Mobile type Double-stage vacuum Transformer oil purifier can remove the water, gas and impurities in insulation oil high-efficiently, increasing the pressure force and quality of oil, make the oil limiting voltage-withstand value much higher and make sure the electric device running safely. The machine is mainly used for electric power department and industries to deal with various oils such as transformer oil, mutual oil, switch oil, dielectric oil, insulating oil and so on. It also can be used for filtration of more than 110KV substation live line work onsite. Meanwhile, as the bridge-type vacuum linking system, Series ZYD-M oil purifier can be used as independent vacuum source with functions of vacuum drying and vacuum oiling.
Comparing with the single stage type, this machine adopts the double stages vacuum system, which can improve the machine working vacuum value highly, so it can remove the water, gas and impurities in insulating oil high-efficiently, increasing and maintain the oil's dielectric strength more higher.
According to fieldwork requirement, this machine equips car wheels, which can be easily moved to any work point by traction. It is especially suitable for purifying oil which locates in fields.
(oil filtration, oil purification, oil treatment, oil purifier, oil filter, oil recycling, oil processing, oil filtering, oil purifying, oil regeneration, oil filteration, oil purify, energy saving, oil processor, oil filter, oil process, oil regenerating, oil restoration, waste oil disposal, oil reclaimed, oil reclaiming, waste oil management, oil regenerate, oil reconditioned, oil reconstituted, oil restituting, oil recovering, oil recondition, oil filters, oil refinery, oil refiner, oil cleaning, oil recycle, oil reclaiming, oil separator, oil recovery, oil recycle, oil reclamation, oil refinery, oil separator, oil separation, oil purifiers, oil recondition)
Technical data |
ZYD-M -30 |
ZYD-M -50 |
ZYD-M -75 |
ZYD-M -100 |
ZYD-M -150 |
ZYD-M -200 |
ZYD-M -300 |
ZYD-M -500 |
ZYD-M -1000 |
Rated Flow rate (L/h) |
1800 |
3000 |
4500 |
6000 |
9000 |
12000 |
18000 |
30000 |
60000 |
Heating Power (kw) |
30 |
42 |
54 |
60 |
84 |
108 |
156 |
225 |
450 |
Total Power (kw) |
33 |
46 |
60 |
67 |
94 |
119 |
173 |
257 |
511 |
Inlet(outlet) Dia.(mm) |
25 |
32 |
40 |
40 |
50 |
50 |
65 |
80 |
100 |
Dimensions(cm) |
L |
1380 |
1500 |
1750 |
1900 |
2100 |
2300 |
2600 |
3200 |
3600 |
W |
1100 |
1200 |
1250 |
1280 |
1300 |
1300 |
1380 |
1500 |
1600 |
H |
1600 |
1650 |
1650 |
1700 |
1800 |
1850 |
1950 |
2100 |
2300 |
Net Weight (kg) |
600 |
800 |
900 |
1050 |
1500 |
1800 |
2200 |
3960 |
4980 |
Notice: Due to different type and components of product, the technical data may vary slightly.
Guarantee Performance Index
Insulation Oil Before Treatment |
After One Time Treatment |
After the Treatment of few Times |
Water Content in the Oil ≤ 50PPm |
≤ 15PPm |
≤ 3~5PPm |
Gas Content in the Oil ≤ 12% |
≤ 0.5% |
≤ 0.1% |
Flash Point ≤ 135 C |
≥135 C |
≥135 C |
Breakdown Voltage ≥35kv |
≥55kv |
≥60 ~75kv |