The ZYB series vacuum oil regeneration system (single vacuum stage) has been specially designed for on site use to completely regenerate insulating oils in energized or de-energized transformers. The ZYB system provides not only the regular oil purification of degassing, drying and particulate removal but also can remove color, acidity, sludge, other soluble oil decay products etc. It is achieved by vacuum technology and filtration system combined with our special additive (physical method). After treated, the oil can be reused as new oil. For special application, the system also can be mounted on a leak proof base and can be installed and operated on a trailer.
Features:
Parameters | Unit | ZYB-20 | ZYB -30 | ZYB -50 | ZYB -100 | ZYB -150 | ZYB -200 |
Capacity | L/h | 1200 | 1800 | 3000 | 6000 | 9000 | 12000 |
Vacuum degree range | Mpa | -0.08~-0.095 | |||||
Working pressure | Mpa | ≤ 0.3 | |||||
Temperature range | ºC | 10~ 80 | |||||
Working noise | dB(A) | ≤68 | ≤70 | ≤72 | ≤75 | ≤80 | ≤80 |
Heating power | kW | 18 | 24 | 30 | 45 | 60 | 72 |
Total power | kW | 22 | 28 | 35 | 50 | 68 | 80 |
Oil inlet (outlet) caliber | mm | Ø25 | Ø25 | Ø32 | Ø42 | Ø50 | Ø50 |
Size | mm | 1500×900×1550 | 1600×900×1650 | 1600×900×1700 | 1600×950×1700 | 1600×950×1800 | 1700×1000×1950 |
Weight | Kgs | 400 | 450 | 600 | 800 | 850 | 900 |
Moisture | PPM | ≤5 |
Gas content | % | ≤0.1 |
Impurity size | μ | ≤1 (no free carbon) |
Breakdown voltage | kV | ≥70 |
IFT | dynes/cm | ≥40 |
Acid value | mgKOH/g | ≤0.03 |
Dielectric loss factors | tgδ(90ºC) | ≤0.001 |