Certification: | CE |
---|---|
Application: | Transformer Oil |
Voltage: | 380V |
Folw Rate: | 30 L/min |
Working Noise: | 75dB(a) |
Heating Power: | 30kw |
Customization: |
---|
Suppliers with verified business licenses
Application:
The Oil regeneration system (Series ZYD-I) has been specially designed for on site use to completely regenerate insulating oils in energized or de-energized transformers. The ZYD-I system provides regular oil purification such as degassing, drying and particulate removal but also can remove acidity, sludge, other soluble oil decay products and discoloration. This is accomplished by the use of high vacuum degasification technology and particulate filters combined with our special brand of earth. After treating, the oil can be reused as new.
Features:
Parameter | Unit | ZYD-I-30 | ZYD-I-50 | ZYD-I-100 | ZYD-I-150 | ZYD-I-200 | ZYD-I-250 | ZYD-I-300 | |||||||
Flow rate | L/h | 1800 | 3000 | 6000 | 9000 | 12000 | 15000 | 18000 | |||||||
Work vacuum | MPa | -0.08~-0.099 | |||||||||||||
Work pressure | MPa | ≤0.3 | |||||||||||||
Temperature | ºC | 20 ~ 80 | |||||||||||||
Power | 3 ph 380V 60Hz (Or as needed) | ||||||||||||||
Working noise | dB(A) | 75 | 75 | 75 | 75 | 80 | 80 | 80 | |||||||
Heating power | kW | 30 | 30 | 45 | 60 | 75 | 90 | 120 | |||||||
Total power | kW | 35.5 | 37.5 | 52.5 | 71.4 | 86.5 | 102.5 | 135 | |||||||
Oil Inlet/Outlet | mm | φ25 | φ32 | φ42 | φ50 | φ50 | φ60 | φ60 | |||||||
Weight | Kg | 600 | 800 | 1050 | 1400 | 1800 | 2000 | 2200 | |||||||
Size | Length | mm | 1050 | 1100 | 1200 | 1450 | 1600 | 1800 | 1900 | ||||||
Width | mm | 750 | 800 | 950 | 950 | 1100 | 1200 | 1200 | |||||||
Height | mm | 1350 | 1400 | 1500 | 1650 | 1800 | 1900 | 1900 |
Item | Unit | After treatment |
Breakdown Voltage | kV | ≥75 |
Moisture content | PPM | ≤3 |
Gas content | % | ≤0.1 |
Impurity size | micron | ≤1 (no free carbon) |
IFT | dynes/cm | ≥40 |
Acid value | mg KOH/g | ≤ 0.03 |
Dielectric loss factors | tgδ(90ºC) | ≤0.001 |
Suppliers with verified business licenses