TTR CT/PT Transformer Turn Ratio Measuring Instruments (TPOM-901)

Condition: New
Power Supply: Customizable
&Nbsp;Weight: &Nbsp;7kg
Size: 400*350*200mm
Power&Nbsp;Supply: AC220V&Nbsp;±&Nbsp;10%,&Nbsp;50Hz
Transport Package: Standard Export Wooden Case Per Set
Customization:
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2020

Suppliers with verified business licenses

Rating: 5.0/5
Chongqing, China
100% Finished Products Inspection
The supplier inspects 100% of finished products.
Standardized quality control
The supplier has a complete and standardized quality control process, check the Audit Report for more information
R&D Capabilities
The supplier has 3 R&D engineers, you can check the Audit Report for more information
Production Process Visualization
You can check the supplier's production workflow chart or main facilities in the Audit Report
to see all verified strength labels (27)

Basic Info.

Model NO.
TPOM-901
Specification
SGS, CE, ISO
Trademark
TOP
Origin
Chongqing, China
HS Code
8421299090
Production Capacity
500 Sets/Month

Product Description

TTR CT/PT transformer turn ratio measuring instrument (TPOM-901)
 
 
Small size and portable;
Low price with reliable performance.

1 Introduction
TPOM-901 is applied to measure the voltage ratio of three or single phase transformer. All the data and test 
results are shown on a 320*240 LCD screen. All the test results could be printed by the micro printer or saved in the storage of the tester. The tester has a good performance on auto protection and anti-disturb. 

2 Main functions
1. The voltage ratio measurement of three or singe phase transformer
2. The group vector measurement of three phase transformer.
3. The polarity measurement of single phase transformer or CT/PT
4. Voltage ratio error calculation 
5. Voltage ratio range calculation of three phase transformer
6. Current transformer ratio measurement
7. Excitation current measurement in ratio testing
8. Reproduction the AC test voltage from power source to reduce the effects of bad power source 
9. Save the test results in the memory internal the tester
10. Print the test results by micro printer
11. Reverse connection detect unit to prevent the high voltage injected to the operate 
12. Over current protection in test voltage
13. Upload the test results to make word report by RS232 interface 
 
3 Technical parameters
Ratio measurement range 1-10000
Group measurement 1-12
Phase measurement error 1 degree
Ratio measurement error 1-2000 ± 0.2%   2000-10000  ± 0.5%
Power supply AC220V ± 10%, 50Hz
Size 400´350´200  mm3     


Trustable technical and after sale serivece
1. Long-term warranty of 2 years.
2. Provide best spare parts at low price (some for free).
3. Provide timely reply and technical support.
4. If anything wrong with the equipment, we would give prompt response and provide solution within 24 hours.
5. If there is technological innovation, we would guide our customer to upgrade.


 [Key words: current transformer analyzer, automatic transformer tester, current transformer tester, transformer turns ratio tester, 3 phase transformer turn ratio tester, CT ratio tester, transformer turn ratio, machinery for transformer testing, transformer tester, ttr transformer turns ratio tester, current transformer analyzer, ct analyzer, test transformer, transformer testing, ttr tester, transformer ttr tester, transformer ct pt testing equipment, resistance tester, phase error test, ctpt current transformer testing equipment, ct pt tester, ct pt transformer tester, ct/pt analyzer, ct pt testing equipment, ttr tester, polarity tester, current transformer transformation ratio test, transformer ct pt testing equipment, distribution transformer testing equipment, power transformer testing equipment, current transformer ratio testing instrument, transformer ttr machine... ] 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now